QUALITROL 104/TR6000 Remote mount thermometer
Reliable liquid or simulated winding indication at eye level

Capillary based, remote indicating, mechanical thermometer. Features bourdon tube measurement with resettable maximum pointer and up to 4 switches for temperature related alarms and control signals. Electronic outputs also available for integration into SCADA and remote monitoring systems.
- Bourdon tube based capillary measurement with resettable maximum pointer
- Up to 2 user adjustable switches (contacts) and one additional fixed switch for control and alarms
- 5 inch (130mm) dial face with an angular dial span of 120° for easy viewing
- Low profile probe can be dressed for use in dry type transformers
Reliable liquid or simulated winding indication at eye level
- Continuously improved design over 40 years of real world experience in substation environment
- North American industry standard, specified more often for liquid or simulated winding temperature measurement than any other thermometer
- ‘Quick-test’ feature enables test switch actuation by simply moving indicating pointer through switch settings, the no-stress spring-loaded clutc
- prevents damage to internal mechanisms
- Capillary system allows the remote indicator with a large 6 inch (150 mm) dial face to be viewed at eye level
Rugged construction and corrosion resistant materials for life-long function
- Die-cast aluminum housing resists corrosion with thermosetting powder coat finish
- Molded neoprene channel gasket uniformly clamped in place, sealing against water entry around entire lens
- Stainless steel bezel ring and probe resist corrosion
- UV stabilized polycarbonate or glass lens options help prevent discoloration of dial face and lens for life-long readability
Wide array of options to fit your exact application
- Wide variety of temperature ranges available for oil (liquid) or simulated winding temperature (winding temperature simulation requires heated well o
- QUALITROL thermal plate)
- Available with up to 4 user-adjustable switches featuring lockdown screws to reduce the effects of vibration and inhibit tampering
- Probe type and size, capillary length, protective armor and mounting styles can all be specified to meet your requirements
- Various electrical connection types, connector cable types, and SCADA outputs (0-1 mA or 4-20 mA) are available
- Models available for bearing temperature and dry-type transformer winding temperature applications
Advanced electronic communications for remote data monitoring
- Optional SCADA analog outputs (0-1 mA and 4-20 mA) with integrated power supplies provide signals for remote monitoring and data acquisition
- Bourdon tube based capillary measurement with resettable maximum pointer
- Up to 2 user adjustable switches (contacts) and one additional fixed switch for control and alarms
- 5 inch (130mm) dial face with an angular dial span of 120° for easy viewing
- Low profile probe can be dressed for use in dry type transformers
- Temperature ranges applicable for oil (liquid) or winding (winding simulation requires heated well or QUALITROL Thermal plate)
- Up to 4 user adjustable switches (contacts)
- Mounting style, tank connection style, probe length, capillary (length, material, protective housing), compatible well
- Electrical connection type, connector cable type and wire colors
- SCADA output (0-1mA or 4-20mA) with integrated power supply
For temperature indication with integrated control and alarm functions. Designed for use where the point of measurement (the well or pocket) is not easily viewed by personnel requiring separate or remote indication.